Applications

May be used as service-entrance conductors and in other applications where SE cables are permitted when installed as specified by NEC® Article 230. May be used in dry, above-ground applications only at temperatures up to 90°C.

  • residential
up arrow

Conductors

Insulated Phase Conductors and Neutral
  • Compact stranded AA-8000 Series aluminum alloy
Bare Equipment Grounding Conductor
  • Compact stranded AA-8000 Series aluminum alloy
up arrow

Insulation

Type XHHW-2 conductors
Black XLP (cross-linked polyethylene), rated 90°C in wet or dry locations
Polarity ID: A red stripe on one conductor’s insulation surface

up arrow

Jacket

Gray, sunlight-resistant PVC (polyvinyl chloride) jacket over the complete assembly

up arrow

Industry Standards

UL® 44 (insulated conductors)
UL® 854 Service Entrance Cables
Federal Specification A-A-59544
NFPA70: National Electrical Code®
RoHS Compliant

up arrow

Assembly

Insulated and bare conductors are twisted together.
A glass-reinforced tape is applied over the conductors.

up arrow

Surface Print

Sample: AA-8000 AL TYPE SE CABLE STYLE R XHHW-2 600V 3 CDRS. 2 AWG 1 CDR. 4 AWG (UL)

up arrow

Product Specifications:

pdf iconView Printable PDF
  Conductors     Allowable Ampacities*    
Product Code Number
Explain Product Codes
AWG Size Bare Equipment Ground AWG Approx. O.D. Inches 75°C**** 90°C**** Dwelling***** Approx. Net Wt. Lbs./M Ft.
536-3600J 6-6-6-6 6 0.650 40 50 55 182
536-4800J 2-2-2-4 4 0.863 75 90 100 346
536-5200J 1-1-1-3 3 0.986 100 115 110 449
536-5600J 1/0-1/0-1/0-2 2 1.061 100 120 135 526
536-6000J 2/0-2/0-2/0-1 1 1.164 115 135 150 637
536-6800T 4/0-4/0-4/0-2/0 2/0 1.390 150 180 205 948
536-6800J 4/0-4/0-4/0-2/0 2/0 1.390 150 180 205 948

If your product code is not listed above, please consult PDF or contact customer service.

*Per Table 310-16 NEC®
**For termination to equipment for circuits rated 100 amperes or less or marked for Nos. 6 through 1 conductors.
***For termination to equipment for circuits rated over 100 amperes or marked for conductors larger than No. 1.
****Dry Locations.
*****For dwelling units, conductors shall be permitted at listed ampacities for 120/240 colt, 3-wire, single-phase service conductors that supply the total load.