Applications

May be used as service-entrance conductors when installed as required by NEC®
Article 230. May be used for branch circuits or feeders within a building as specified by
the NEC Section 338-10.

  • branch circuit wiring
  • residential
up arrow

Conductors

Conductors
  • Compact stranded AA-8000 Series aluminum alloy
Grounding Conductor
  • Bare conductor strands are helically wound around two paralleled insulated conductors.
up arrow

Insulation

Type XHHW-2 conductors
Black XLP (cross-linked polyethylene), rated 90°C in wet or dry locations
Polarity ID: A red stripe on one conductor’s insulation surface

up arrow

Jacket

Gray, sunlight-resistant PVC (polyvinyl chloride) over entire assembly

up arrow

Industry Standards

UL Standard 44 (Insulated Conductors)
UL 854 Service Entrance Cables
Federal Specification A-A-59544
NFPA70: National Electrical Code®

up arrow

Assembly

Glass-reinforced tape applied over conductors

up arrow

Surface Print

Sample: AA-8000 AL TYPE SE CABLE STYLE U XHHW-2 660V 2 CDRS 2 AWG 1 CDR 4AWG (UL)

up arrow

Product Specifications:

pdf iconView Printable PDF
        Allowable Ampacities*    
Product Code Number
Explain Product Codes
2 Conductors AWG Concentric AWG Approx. O.D. Inches 60°C** 75°C*** 90°C**** Dwelling***** Approx. Net. Wt. Lbs./M Ft.
530-3600J 6-6 6 .458 x .720 40 50 60 - 143
530-3600T 6-6 6 .458 x .720 40 50 60 - 143
530-4600J 2-2 4 .554 x .910 75 90 100 100 259
530-4800J 2-2 2 .559 x .919 75 90 100 100 282
530-5200J 1/0-1/0 1/0 .680 x .1.125 100 120 135 135 428
530-6000J 2/0-2/0 2/0 .736 x 1.221 115 135 150 150 514
530-6600J 4/0-4/0 2/0 .835 x 1.419 150 180 205 205 691
530-6800G 4/0-4/0 4/0 .857 x 1.445 150 180 205 200 762
530-6800J 4/0-4/0 4/0 .857 x 1.445 150 180 205 200 762

If your product code is not listed above, please consult PDF or contact customer service.

*Per Table 310-16 NEC®
**For termination to equipment for circuits rated 100 amperes or less or marked for size 14 through 1 conductors.
***For termination to equipment for circuits rated over 100 amperes or marked for conductors larger than No. 1.
****Dry Locations.
*****For dwelling units, conductors shall be permitted at listed ampacities for 120/240 colt, 3-wire, single-phase service conductors that supply the total load.