Applications

May be used as service-entrance conductors when installed as required by NEC® Article 230. May be used for branch circuits or feeders within a building as specified by the NEC Section 338-10.

  • branch circuit wiring
  • feeders
  • service entrance
  • wet or dry locations
up arrow

Conductors

Stranded Conductors:
  • Uncoated copper per ASTM-B3, ASTM-B8, and ASTM-B787
Insulated Conductors:
  • Type THHN conductors
    Black PVC (polyvinyl chloride), rated 90°C in wet or dry locations
    Jacketed with black nylon (polyamide)
    Polarity ID: A red stripe on one conductor’s insulation surface
Neutral Conductor
  • Stranded, uncoated copper per ASTM-B3, ASTM-B8, and ASTM-B787
up arrow

Jacket

Gray, sunlight-resistant PVC (polyvinyl chloride) over entire assembly

up arrow

Industry Standards

UL 83 (Insulated Conductors)
UL 854 Service Entrance Cables, FILE NO. 11098
ASTM-B3
ASTM-B8
ASTM-B787
Federal Specification A-A-59544
NFPA70: National Electrical Code®

up arrow

Assembly

Parallel-laid conductors with the neutral conductor between the two insulated conductors. Conductors are wrapped with a fiberglass-reinforced polyester tape.

up arrow

Surface Print

Sample: TYPE SE CABLE STYLE U TYPE THHN OR THWN CDRS 2 CDRS? 6 AWG 1 CDR 8 AWG 600V E11098-A (UL)

Where to Buy:

Please note NOT all products are sold in all locations. To confirm availability, please contact Customer Service.

up arrow

Product Specifications:

pdf iconView Printable PDF
  2 Conductors Bare Neutral   Allowable Ampacities*    
Product Code Number
Explain Product Codes
AWG Size No. of Strands AWG Size No. of Strands Approx. O.D. Strands 60°C** 75°C*** 90°C**** Dwelling***** Approx. Net. Wt. Lbs./M Ft.
130-3200G 8-8 7 8 7 400 x 710 40 50 55 - 241
130-3200J 8-8 7 8 7 400 x 710 40 50 55 - 241
130-3400F 6-6 7 8 7 400 x 770 55 65 75 - 313
130-3400J 6-6 7 8 7 400 x 770 55 65 75 - 313
130-3600E 6-6 7 6 7 400 x 790 55 65 75 - 348
130-3600J 6-6 7 6 7 400 x 790 55 65 75 - 348
130-3800E 4-4 7 6 7 470 x 950 70 85 95 100 486
130-3800J 4-4 7 6 7 470 x 950 70 85 95 100 486
130-4000E 4-4 7 4 7 470 x 1030 70 85 95 100 533
130-4000J 4-4 7 4 7 470 x 1030 70 85 95 100 533
130-4200J 3-3 7 5 7 500 x 1040 85 100 110 110 588
130-4400J 3-3 7 3 7 500 x 1050 85 100 110 110 647
130-4600J 2-2 7 4 7 565 x 1100 95 115 130 125 721
130-4800J 2-2 7 2 7 565 x 1200 95 115 130 125 802
130-6000J 2/0-2/0 19 2/0 19 900 x 1400 145 175 195 200 1412

If your product code is not listed above, please consult PDF or contact customer service.

*Per Table 310-16 NEC®
**For termination to equipment for circuits rated 100 amperes or less or marked for size 14 through 1 AWG conductors.
***For termination to equipment for circuits rated over 100 amperes or marked for conductors larger than 1 AWG.
****Dry locations.
*****For dwelling units, conductors shall be permitted at listed ampacities for 120/240 volt, 3-wire, single-phase service conductors that supply the total load. Per Table 310-15(B)(6) NEC®.